Two Kingdom Street
Summary Specification


  • Four pipe (chilled water and LTHW) fan coil air conditioning system with DC motors provided at the perimeter, with cooling only fan coil units provided in the internal zones.
  • Fully accessible raised floor - 100mm clear void
  • Perforated, removable metal ceiling tiles with integrated lighting, smoke detection, supply and extract grilles
  • Lighting designed to comply with the CIBSE/SLL LG7 code, incorporating presence detection and intelligent lighting controls
  • Small power 5W/ sq m plus 5W/sq m on-floor upgrade allowance
  • Ventilation provision of 1.2 l/s/sq m
  • 1.5m planning grid with services positioned to allow for flexible office partitioning
  • 2.8m floor to ceiling height
  • General floor loadings of 3.5kN/sq m plus 1kN/sq m partition loading
  • Enhanced floor loadings of 7.5kN/ sq m to certain areas
  • 6 semi scenic passenger lifts serving the podium to ninth office floors (maximum rated capacity up to 2,000 kg each, at 2.5m/s)
  • 1 studios/offices passenger and fire lift (630 kg) serving level-2 to 9th floor
  • 1 dedicated office fire lift (630 kg) serving level -2 to 9th floor
  • 2 goods lifts (2,250 kg), one serving level -2 to roof level, one serving the studio accommodation at level -2 to level -1 only.
  • 1 car park shuttle lift (630 kg) serving level -2 to podium level only
  • 19 office car parking spaces, 2 studio car parking spaces